Wind turbine (signal model)#

block

Block appearance in REPEAT VISION#

 The Wind turbine (signal model) block implements an aerodynamic signal model of a wind turbine and calculates the speed factor, power factor, mechanical power and mechanical torque from input signals and specified parameters. Depending on the selected mode, the power factor is determined by an analytical dependence, a tabular characteristic, or is set by an external signal.

Hint

The block can be used together with various electrical machines from the Electronics and Electrocity libraries.

 The output power of a wind turbine is generally described by the expression (1) [1]:

(1)#\[P=\frac{1}{2}\cdot C_p(\beta, \lambda) \cdot p \cdot A \cdot V^3\]

where:

 \(C_p(\beta, \lambda)\) – power factor (or wind energy utilization factor);

 \(p\) — air density, [kg/m\(^3\)];

 \(\beta\) – blade rotation angle, [deg.];

 \(\lambda\) – speed coefficient (the ratio of the linear speed of the blade tip to the wind speed);

 \(A=\pi \cdot R^2\) – swept area, [m\(^2\)]. Calculated from the value for \(R\) specified by the user in the Rotor radius property in [m];

 \(V\) – wind speed, [m/s].

Important

The wind speed value is set using the input port Wind speed. The block aerodynamic models are designed for non-negative wind speeds; behavior outside this region should not be interpreted as a physical model of reverse airflow.

The mechanical torque on the shaft of an electric machine is calculated using the formula (2):

(2)#\[T_m=-\frac{p}{\omega}\]

where \(\omega\) is the angular velocity of the machine [rad/s].

 In the formula (2), the - sign corresponds to the direction of the mechanical moment adopted in the block: with a positive angular velocity of the machine and positive mechanical power, the moment transmitted to the electric machine has a negative sign.

1.  SI units and per-units#

 For ease of connecting the unit to various models of electrical machines, the angular velocity of the machine can be specified in named or relative units (depending on the value of the Machine angular speed input property), and the mechanical torque and mechanical power can be output in one of these formats (depending on the value of the Mechanical output format property).

 The transition between named and relative units is performed in accordance with table 1.

Table 1

Magnitude

Value in r.u.

Basic value

Angular velocity of the machine

\(\omega_{pu}=\omega/ \omega_{base}\)

\(\omega_{base}\) – the value of the property Machine base angular speed, [rad/s]

Mechanical output power

\(P_{pu}=P/ S_{base}\)

\(S_{base}\) – value of the property Machine base apparent power, [VA]

Mechanical torque

\(T_{pu}=T/ T_{base}\),
where \(T_{base}=S_{base}/ \omega_{base}\)

\(T_{base}\) – basic mechanical moment, [N·m]

 When parameterizing By nominal turbine data, the relative power value in the formula (3) is determined relative to the nominal mechanical power of the turbine. When calculating mechanical power in relative units, the base apparent power of the electric machine is used. Therefore, the values ​​of \(P_{pu\hspace{1mm} turb}\) and \(P_{pu}\) generally do not coincide.

2.  Parameterization method#

 Depending on the value of the Parameterization method property, the block requires setting wind turbine parameters of various types. These modes also use different methods for determining the turbine’s power factor.

2.1.  Parameterization method – «Based on turbine nominal data»#

 In this case, it is necessary to set the nominal power of the turbine and a number of parameters for calculating the mechanical power in [r.u.] using the formula (3):

(3)#\[P_{pu\hspace{1mm}turb}=k_p \cdot C_{p\hspace{1mm}pu} \cdot V^3_{pu}\]

where:

 \(P_{pu\hspace{1mm}turb}\) – mechanical power, related to the nominal mechanical power of the turbine, [r.u.];

 \(k_p\) – maximum power at the base wind speed in relative units in relation to the nominal mechanical power of the turbine, [r.u.]. For \(C_{p\hspace{1mm}pu}=1\) and \(V_{pu}=1\) this power is usually less than or equal to 1 [r.u.] and is determined by the value of the property Maximum power at base wind speed;

 \(C_{p\hspace{1mm}pu}=\frac{C_p}{C_{p\hspace{1mm}max}}\) – the value of the calculated power factor in relation to the maximum value of the power factor \(C_{p\hspace{1mm}max}\)=0.48 according to [1], [r.u.];

 \(V_{pu}=\frac{V}{V_{base}}\) – wind speed relative to the base wind speed \(V_{base}\) specified by the user in the Base wind speed property, [r.u.].

 The power factor in the formula (3) is calculated using the empirical expression (4) [1]:

(4)#\[C_p=0.51763 \cdot (\frac{116}{\lambda_i}-0.4 \cdot \beta -5)\cdot e^{-\frac{21}{\lambda_i}}+0.006795 \cdot \lambda\]

where:

 \(\frac{1}{\lambda_i}=\frac{1}{\lambda + 0.008 \cdot \beta}-\frac{0.035}{\beta^3+1}\) – the value inverse to the speed coefficient;

 \(\lambda=\lambda_{nom} \cdot \frac{\omega_{pu}}{\omega_{pu\hspace{1mm}Pmax}\cdot V_{pu}}\) – speed coefficient relative to its nominal value \(\lambda_{nom}=8.1\) according to [1];

 \(\omega_{pu\hspace{1mm}Pmax}\) – relative rotation speed corresponding to the maximum turbine power at the base wind speed, [r.u.]. Determined by the value of the property Rotational speed at maximum power for base wind speed.

 Fig. 1 shows the dependences of the power factor \(C_p\) on the speed coefficient \(\lambda\), calculated using the formula (4) for different values ​​of the blade rotation angle \(\beta\).

Fig. 1 Dependence of Cp on λ for different β for parameterization using nominal turbine data

Fig. 1 Dependence of Cp on λ for different β for parameterization using nominal turbine data#

 At \(\beta = 0\), the maximum value of the power factor is \(C_{p\hspace{1mm}max}=0.48\) and is achieved at \(\lambda≈ 8.1\)

 When the angle of rotation of the blades changes, both the maximum value of the power factor and the position of the maximum of the characteristic change. Due to this, changing the angle \(\beta\) can be used to control the mechanical power of the wind turbine.

2.2.  Parameterization method – «Based on turbine physical parameters»#

 In this case, you need to specify the turbine blade radius and air density. The turbine power is calculated using the formula (5):

(5)#\[P=\frac{1}{2}\cdot C_p \cdot p \cdot A \cdot V^3 \cdot \eta_{GB}\]

where:

 \(\eta_{GB}\) – Efficiency of the gearbox;

Note

If the Enable gearbox property is Off, then in the formula (5) \(\eta_{GB}\) is taken to be equal to 1.

 \(C_p\) – power factor determined depending on the value of the property Power coefficient determination method.

 The Power coefficient determination method property provides various methods for calculating \(C_p\), as shown in table 2.

Table 2

Method for determining the power factor

Calculation of the speed coefficient

Definition of \(C_p\)

Purpose and features

Three-bladed turbine (MOD 2)

According to the formula (6)

According to the empirical dependence (7) [2]

Suitable for modeling three-bladed horizontal axis wind turbines

Two-bladed turbine (MOD 5)

According to the formula (8)

According to the empirical dependence (9) [3]

Suitable for modeling horizontal axis wind turbines with two blades

Tabulated characteristic

Smoothed value using the formula (10)

Linear interpolation using the table \(C_p(\beta, \lambda)\)

Allows you to set a custom aerodynamic characteristic

External input

According to the formula (8), only for display in the sensor

Set by the input signal

Does not require calculation of \(C_p\) inside the block

 The calculation in each mode is performed as follows:

  • Three-bladed turbine (MOD 2) – in this mode, the speed coefficient is calculated using the formula (6), and the turbine power coefficient is calculated using the empirical dependence (7) [2]:

(6)#\[\gamma=2.237 \cdot \frac{V}{\omega_H}\]
(7)#\[C_p=0.5 \cdot (\gamma - 5.6 - 0.022 \cdot \beta^2) \cdot e^{-0.17 \cdot \gamma}\]

where:

 \(\gamma\) – speed coefficient, [(mph)/(rad/s)];

 \(\omega_H=\frac{\omega}{GR}\) – angular velocity of the turbine rotor taking into account the gear ratio of the reducer, [rad/s];

 \(GR\) – gear ratio of the gearbox.

Note

If the Enable gearbox property is Off, then in the formula (6) \(GR\) is taken to be equal to 1.

  • Two-bladed turbine (MOD 5) – in this mode, the speed coefficient is calculated using the formula (8), and the turbine power coefficient is calculated using the empirical dependence (9) [3]:

(8)#\[\lambda=\frac{\omega_H \cdot R}{V}\]
(9)#\[C_p=(0.44-0.0167 \cdot \beta)\cdot sin(\frac{\frac{\pi}{2} \cdot (\lambda-3)}{7.5 - 0.15 \cdot \beta})-0.00184 \cdot \beta \cdot (\lambda-3)\]

Important

In the formula (9) the expression \(7.5-0.15 \cdot \beta\) at \(\beta=50^o\) is equal to zero, therefore, when setting such a value for the angle in the block, an error will occur and the calculation will be stopped.

 If the speed factor calculated using the formula (8) is less than 0, then the limiting value \(\lambda=0\) is used to calculate the power factor using the formula (9), since the dependence of the power factor is not \(\lambda=0\), since the dependence of the power factor is not extrapolated into the region of negative values ​​of the speed factor. In this case, the Speed ​​coefficient sensor displays the value of \(\lambda\) directly calculated using the formula (8).

Important

The number of elements in the Pitch angle vector β property must match the number of rows in the Power coefficient table \(C_p\)(β,λ) property, and the number of elements in the Tip speed ratio vector λ property must match the number of columns in the power factor table. Each of the vectors must contain at least two elements, and the values ​​of the elements must be strictly increasing.

 For this mode, the smoothed speed coefficient \(\lambda_{smooth}\) is calculated using the formula (10) :

(10)#\[\lambda_{smooth}=\frac{\omega_H \cdot R \cdot V}{(V^2 + V^2_{thr})}\]

where \(V_{thr}\) is the wind speed smoothing threshold, [m/s]. This ensures the continuity of the calculation of the speed coefficient and power near zero wind speed.

 Based on the signal from the port Pitch angle β, degrees and the value of the smoothed speed coefficient calculated using the formula (10), the value \(C_p\) is calculated using linear interpolation according to the data in the power factor table and is then used to calculate the smoothed value of power and torque using the formulas (11) and (12) :

(11)#\[P_{smooth}=\frac{1}{2} \cdot C_p \cdot p \cdot A \cdot (V^2 + V^2_{thr})^{3/2}\cdot \eta_{GB}\]
(12)#\[T_{m\hspace{1mm}smooth}=-\frac{P_{smooth}}{\sqrt{\omega^2 + \omega^2_{thr}}}\]

where \(\omega_{thr}\) is the machine angular velocity smoothing threshold, [rad/s]. It is used when calculating the torque to prevent division by an angular velocity value close to zero.

 When the values ​​of \(\beta\) and \(\lambda_{smooth}\) go beyond the ranges specified by the corresponding vectors, the argument is limited to the nearest boundary value; extrapolation beyond the table characteristic is not performed. In this case, the Speed ​​coefficient sensor displays the value \(\lambda_{smooth}\) calculated using the formula (10) until it is limited by the range of the table characteristic.

 In this mode, when the machine shaft rotates in the opposite direction, the calculated mechanical power is smoothly suppressed to zero, as a result of which the mechanical torque also decreases. The transition occurs in the region of negative angular velocities from \(\omega=0\) to \(\omega = - \omega_{thr}\), and for \(\omega<- \omega_{thr}\) the suppression becomes almost complete. For direct rotation, the effect of this suppression is negligible.

  • External input – in this mode, the power factor is set by an external signal via the Power coefficient \(C_p\) port. In this case, the value calculated using the formula (8) is output to the Speed ​​coefficient sensor, but is not used in further calculations.

3.  Properties#

Property

Default Value

Description

Units of measurement

Parameterization method:
Based on turbine nominal data;
Based on turbine physical parameters

Based on turbine nominal data

–

–

Machine angular speed input:
SI units;
Per-unit

SI units

–

–

Mechanical output format:
SI units;
Per-unit

SI units

–

–

Nominal turbine mechanical power

1.5e6

Available, when Parameterization method - Based on turbine nominal data

W

Machine base apparent power

1.667e6

–

VA

Machine base angular speed

157.08

–

rad/s

Base wind speed

12

Available, when Parameterization method - Based on turbine nominal data

m/s

Maximum power at base wind speed

0.73

Available, when Parameterization method - Based on turbine nominal data

r.u.

Rotational speed at maximum power for base wind speed,
available, when Parameterization method - Based on turbine nominal data

1.2

Rotational speed at maximum turbine power for the base wind speed, in [r.u.] of the machine base angular speed.

r.u.

Rotor radius

34

Available, when Parameterization method - Based on turbine physical parameters

m

Air density

1.225

Available, when Parameterization method - Based on turbine physical parameters

kg/m\(^3\)

Enable gearbox

On

Available, when Parameterization method - Based on turbine physical parameters

–

Gearbox efficiency

0.97

Available, when Parameterization method - Based on turbine physical parameters and Enable gearbox - On

r.u.

Gear ratio,
available, when Parameterization method - Based on turbine physical parameters and Enable gearbox - On

50

Ratio of the machine shaft angular speed to the turbine rotor angular speed.

–

Power coefficient determination method:
Three-bladed turbine (MOD 2);
Two-bladed turbine (MOD 5);
Tabulated characteristic;
External input

Three-bladed turbine (MOD 2)

Available, when Parameterization method - Based on turbine physical parameters

–

Pitch angle vector β

0.0;3.0;5.0;10.0;20.0;90.0

Available, when Parameterization method - Based on turbine physical parameters and Power coefficient determination method - Tabulated characteristic

degrees

Tip speed ratio vector λ

0.0;2.0;4.0;6.0;8.0;10.0;12.0;14.0;15.0

Available, when Parameterization method - Based on turbine physical parameters and Power coefficient determination method - Tabulated characteristic

–

Power coefficient table \(C_p\)(β,λ)

<0.001;0.0161;0.1446;0.3865;0.5009;0.4404;0.2545;2.0E-4;-0.1384><0.0016;0.0173;0.1079;0.2676;0.3779;0.4111;0.3838;0.3176;0.2753><0.0027;0.0197;0.1151;0.2606;0.3469;0.3558;0.3069;0.2222;0.1718><0.0054;0.0283;0.1315;0.2364;0.2589;0.2022;0.0929;-0.0455;-0.1204><0.0109;0.0536;0.132;0.1256;0.012;-0.1752;-0.4017;-0.6435;-0.7655>
_<-0.01;-0.01;-0.01;-0.01;-0.01;-0.01;-0.01;-0.01;-0.01>

Available, when Parameterization method - Based on turbine physical parameters and Power coefficient determination method - Tabulated characteristic

–

Wind speed smoothing threshold

0.01

Available, when Parameterization method - Based on turbine physical parameters and Power coefficient determination method - Tabulated characteristic

m/s

Machine angular speed smoothing threshold

0.01

Available, when Parameterization method - Based on turbine physical parameters and Power coefficient determination method - Tabulated characteristic

rad/s

4.  Inputs and outputs#

Parameters

Input/Output

Description

Units of measurement

Port type

Angular velocity of the machine

Input

Available, when Machine angular speed input – SI units

rad/s

Automation

Angular velocity of the machine

Input

Available, when Machine angular speed input – Per-unit

r.u.

Automation

Pitch angle β

Input

Available in all modes except, when Parameterization method - Based on turbine physical parameters and Power coefficient determination method – External input

degrees

Automation

Wind speed

Input

–

m/s

Automation

Power coefficient\(C_p\)

Input

Available, when Parameterization method - Based on turbine physical parameters and Power coefficient determination method – External input

–

Automation

Mechanical torque

Output

Available, when Mechanical output format – SI units

N·m

Automation

Mechanical power

Output

Available, when Mechanical output format – SI units

W

Automation

Mechanical torque

Output

Available, when Mechanical output format – Per-unit

r.u.

Automation

Mechanical power

Output

Available, when Mechanical output format – Per-unit

r.u.

Automation

In order to see the connection capabilities of the block, you need to go to page Description of block ports

5.  Sources#