Generator relay protection#

block

Block appearance in REPEAT VISION#

 Relay protection (RP) is a set of systems that provide automatic detection of faults (SC, overloads, and power failures) and shutdown of the generator to prevent serious accidents.

 The unit implements TOP of the generator, protection against increased voltage during generator idle running, protection against increased and decreased frequency, protection against reverse power.

1.  Properties#

Property

Default Value

Description

Units of measurement

Generator overcurrent current setting

1000

–

А

Generator overcurrent time setting

0.5

–

s

Voltage setting for overvoltage protection at generator idling

1000

–

V

Overvoltage protection current setting at generator idling

1000

–

А

Time setting for protection against overvoltage at generator idling

3

–

s

Upper frequency limit

52

–

Hz

Lower frequency limit

48

–

Hz

Over/underfrequency protection time setting

10

–

s

Active power setting

800

–

MW

Reverse power protection time setting

3

–

s

2.  Inputs and outputs#

Parameters

Input/Output

Description

Units of measurement

Port type

Total generator current

Input

–

А

Automation

Generator voltage

Input

–

V

Automation

Generator frequency

Input

–

Hz

Automation

Generator circuit breaker status

Input

–

–

Automation

Generator active power

Input

–

W

Automation

Turn off the switch

Output

–

–

Automation

In order to see the connection capabilities of the block, you need to go to page Description of block ports