Lumped load (dynamic model)#

block

Block appearance in REPEAT VISION#

 This block is an electrical load, represented in calculations by a variable shunt resistance depending on the effective value and frequency of the voltage in the connection node. The value of this resistance is calculated using the following formula (1):

(1)#\[ Z(U,\Delta f)\:=\:R(U,\Delta f)\:+j \cdot X(U,\Delta f)\:=\:\frac{U^2}{P(U,\Delta f)}\:+\:j\cdot\:\frac{U^2}{Q(U,\Delta f)} \]

where:

 \(U\) - voltage in the load node, [kV];

 \( P\left(U,∆f\right)\) and \( Q\left(U,∆f\right)\) - dependence of active [MW] and reactive [MVAr] powers consumed by the load on the effective value and frequency deviation of the voltage in the connection node. These dependencies are determined in accordance with the following formulas (2):

\[ P(U,\Delta f)\:=\:P_{ном}\:\cdot\:(a_{0}\:+\:a_{1}\:\cdot\:\frac{U}{U_{ном}}\:+\:a_{2}\:\cdot\:\frac{U}{U_{ном}}^2\:+\:a_{3}\:\cdot\:\frac{U}{U_{ном}}^3\:+\:a_{4}\:\cdot\:\frac{U}{U_{ном}}^4\:+\:K_{P}\:\cdot\:\frac{(f\:-\:f_{ном})}{f_{ном}}); \]
(2)#\[ Q(U,\Delta f)\:=\:Q_{ном}\:\cdot\:(b_{0}\:+\:b_{1}\:\cdot\:\frac{U}{U_{ном}}\:+\:b_{2}\:\cdot\:\frac{U}{U_{ном}}^2\:+\:b_{3}\:\cdot\:\frac{U}{U_{ном}}^3\:+\:b_{4}\:\cdot\:\frac{U}{U_{ном}}^4\:+\:K_{Q}\:\cdot\:\frac{(f\:-\:f_{ном})}{f_{ном}}) \]

where:

 \(P_{rat}\) и \(Q_{rat}\) - nominal values of active [MW] and reactive [MVAr] powers;

 \(f\) - frequency value in the load connection assembly, [Hz];

 \(f_{rat}\) - rated value of frequency, assumed to be 50 [Hz];

 \(a_{0},a_{1},a_{2},a_{3},a_{4}\) - coefficients that take into account ratios between different types of active load;

 \(b_{0},b_{1},b_{2},b_{3},b_{4}\) - coefficients considering ratios between different types of reactive load;

 \(K_{P}\) и \( K_{Q}\) - coefficients that take into account the regulation coefficient of active and reactive loads by frequency.

 This model is only applicable to the calculation of dynamic processes in electrical systems.

1.  Properties#

Property

Default value

Description

Units of measurement

Rated active power

10.0

–

MW

Rated reactive power

5.0

–

MVAr

Rated voltage

10.0

–

kW

a\(_0\) constant

0.55

–

–

a\(_1\) constant

-0.3

–

–

a\(_2\) constant

0.47

–

–

a\(_3\) constant

-0.22

–

–

a\(_4\) constant

0.5

–

–

K\(_P\) constant

1.1

–

–

b\(_0\) constant

2.9

–

–

b\(_1\) constant

-8.1

–

–

b\(_2\) constant

6.2

–

–

b\(_3\) constant

-4.2

–

–

b\(_4\) constant

3.2

–

–

K\(_Q\) constant

-1.5

–

–

Rated frequency

50.0

–

Hz

2.  Inputs and outputs#

Parameters

Input/Output

Description

Units of measurement

Port type

Input

Input

–

–

Electrocity

In order to see the connection capabilities of the block, you need to go to page Description of block ports