Three-Winding Transformer#
Block appearance in REPEAT VISION#
Note
When adding a block to the canvas, a window appears with a choice of the required configuration, which allows you to:
Select a ready-made template with settings for a specific brand of transformer;
Select customizable configuration
Configuration selection window#
The Three-winding transformer block is designed for conversion of AC voltage into two other voltage systems by means of electromagnetic induction in accordance with the set transformation ratios without frequency change.
Note
The conversion is non-ideal due to natural losses in transformer steel and windings.
Equivalent circuit of the three-winding transformer shown below (see Fig. 1) is suitable for simulation of steady-state modes and electromechanical transients:
Fig. 1 Three-winding transformer equivalent circuit#
All values of the equivalent circuit parameters are calculated based on the catalog data of the transformer:
the active resistances of the windings are determined on the basis of the loss power during corresponding short-circuit experiments and brought to the higher voltage side: (1):
where:
similarly the impedance of the windings is determined (2):
where:
the winding reactances are determined from the total and active resistances (3):
the active and reactive shunt resistances are calculated from catalog values of the no-load operation (4):
1. Properties#
Property |
Default value |
Description |
Units of measurement |
|---|---|---|---|
Rated power |
6 |
Rated power of the primary winding |
MVA |
Rated voltage of the tertiary winding |
6.3 |
Rated voltage of the tertiary winding |
kV |
Rated voltage of the secondary winding |
10 |
Rated voltage of the secondary windin |
kV |
Rated voltage of the primary winding |
35 |
Rated voltage of the primary winding |
kV |
Short-circuit voltage P-S |
7.5 |
Short-circuit voltage with shorted primary and secondary windings as a percentage of the rated voltage |
% |
Short-circuit voltage P-T |
10 |
Short-circuit voltage with shorted primary and tertiary windings as a percentage of the rated voltage |
% |
Short-circuit voltage S-T |
16.5 |
Short-circuit voltage with shorted secondary and tertiary windings as a percentage of the rated voltage |
% |
Short-circuit power losses P-S |
3 |
Short-circuit power with shorted primary and secondary windings |
kW |
Short-circuit power losses P-T |
4 |
Short-circuit power with shorted primary and tertiary windings |
kW |
Short-circuit power losses S-T |
5 |
Short-circuit power with shorted secondary and tertiary windings |
kW |
Incorporate no load power losses |
Off |
- |
- |
No load power losses |
43 |
idle run losses (losses in steel) |
kW |
No-load current |
0.6 |
idle current as a percentage of the rated current of the HV winding |
% |
2. Inputs and outputs#
Parameters |
Input/Output |
Description |
Units of measurement |
Port type |
|---|---|---|---|---|
Input voltage of the primary winding |
Input |
- |
V |
Elecrocity |
Output voltage of the secondary winding |
Output |
- |
V |
Elecrocity |
Output voltage of the tertiary winding |
Output |
- |
V |
Elecrocity |
In order to see the connection capabilities of the block, you need to go to page Description of block ports