Single-phase linear transformer (Two windings)#

block

Block appearance in REPEAT VISION#

 The Single-phase linear transformer (Two windings) block is a linear model of a single-phase double-winding transformer. The transformer equivalent circuit is shown in Fig. 1:

Fig. 1 Transformer equivalent circuit

Fig. 1 Transformer equivalent circuit#

 This model is based on an ideal transformer the primary winding of which is connected to the magnetization branch with parameters R\(_M\), L\(_M\) and active-inductive resistance with parameters R\(_1\), L\(_1\). Secondary winding is connected to active-inductive resistance with parameters R\(_2\), L\(_2\).

 Taking into account the above circuit, a two-winding single-phase transformer is described by the following system of equations (1):

\[I_1-I_{MR}-I_{ML}=K\cdot I_2\]
\[K\cdot (U_1-(I_1\cdot R_1 + L_1 \cdot \frac{dI_1}{dt}))=U_2\]
\[I_2 \cdot R_2+L_2 \cdot \frac{dI_2}{dt}=U_2\]
(1)#\[U_M=I_{MR}\cdot R_M=L_M \cdot \frac{dI_{ML}}{dt}\]

where:

 \(U_1\), \(U_2\) - voltage of the primary and secondary windings, respectively, [V];

 \(I_1\), \(I_2\) - currents of primary and secondary windings respectively, [A];

 \(I_{ML}\) - inductive component of the magnetization branch current, [A];

 \(I_{MR}\) - active component of the magnetization branch current, [A];

 \(U_M\) - voltage on the magnetization branch, [V];

 \(R_1\), \(R_2\) - active resistances of primary and secondary windings respectively, [Ohm];

 \(L_1\), \(L_2\) - inductance of primary and secondary windings respectively, [H];

 \(R_M\) - active resistance of the magnetization branch, [Ohm];

 \(L_M\) - inductance of the magnetization branch, [H];

 K - transformation ratio of an ideal transformer.

 The model has various ways of model parameters:

  • Setting the parameters in SI system (then it is necessary to set only windings parameters (rated voltages, [V], active resistances, [Ohm] and spreading inductances, [H]; inductance of windings and mutual inductance are calculated inside the block));

  • Setting of parameters in relative units (then it is necessary to set only winding parameters (rated voltages, [V], active resistances, [r.u.] and scattering inductance, [r.u.]; winding inductance and mutual inductance are calculated inside the block, and winding parameters will be recalculated into named units));

  • Set catalog parameters (equivalent circuit parameters will be calculated automatically).

 The procedure for calculating equivalent circuit parameters from relative units and catalog data is given in the corresponding article.

1.  Properties#

Property

Default Value

Description

Units of measurement

Model parameter:
SI;
PU;
Specification

SI

-

-

Primary winding parameters, available, when Model parameter - SI

230.0e3;4.3218;0.45856

Data structure: \(U_{1nom}\);\(R_1\);\(L_1\)

V; Ohm; H

Secondary winding parameters, available, when Model parameter - SI

115.0e3;0.7938;0.084225

Data structure: \(U_{2nom}\);\(R_2\);\(L_2\)

V; Ohm; H

Magnetizing branch parameters, available, when Model parameter - SI

1080400;2866

Data structure: \(R_M\);\(L_M\)

Ohm; H

Nominal power

250.0e6

Available, when Model parameter - PU or Specification

VA

Nominal frequency

50.0

Available, when Model parameter - PU or Specification

Hz

Primary winding parameter, available, when Model parameter - PU

230.0e3;4.3218;0.45856

Data structure: \(U_{1nom}\); \(R_1\); \(L_1\)

V; r.u.; r.u.

Secondary winding parameters, available, when Model parameter - PU

115.0e3;0.7938;0.084225

Data structure: \(U_{2nom}\);\(R_2\);\(L_2\)

V; r.u.; r.u.

Magnetizing branch parameters, available, when Model parameter - PU

500;500

Data structure: \(R_M\);\(L_M\)

r.u.; r.u.

Nominal voltage of primary winding

230.e3

Available, when Model parameter - Specification

V

Nominal voltage of secondary winding

115.e3

Available, when Model parameter - Specification

V

Nominal short-circuit loss

35.e3

Available, when Model parameter - Specification

W

Nominal impedance voltage

10.5

Available, when Model parameter - Specification

%

Nominal no load loss

10.e3

Available, when Model parameter - Specification

W

Nominal no-load current

0.5

Available, when Model parameter - Specification

%

Initial values of windings currents

0.0;0.0

Data structure: \(I_{10}\);\(I_{20}\)

А

Initial conditions for magnetizing branch

0.0;0.0

Data structure: \(I_{MO}\);\(U_{MO}\)

A; V

2.  Inputs and outputs#

Parameters

Input/Output

Description

Units of measurement

Port type

1+

Input

-

-

Electronics

1-

Output

-

-

Electronics

2+

Input

-

-

Electronics

2-

Output

-

-

Electronics

In order to see the connection capabilities of the block, you need to go to page Description of block ports