Power line#

block

Block appearance in REPEAT VISION#

 The Power line block is intended for simulation of an overhead orcable line having a U-shaped equivalent circuit. The line equivalent circuit shown below (see Fig. 1) takes into account the following physical phenomena:

  • conductor heating and inductance of the line phases with respect to ground(simulated by longitudinal R and X [Ohm], respectively);

  • active losses due to corona effect and current leakage through insulators - activeconductivity G [S];

  • displacement currents caused by electrostatic field between conductor phasesand ground - capacitive conductivity B [S].

Fig. 1 PTL equivalent circuit

Fig. 1 PTL equivalent circuit#

 Depending on the voltage class of the network to which the simulated line belongs,the active and/ or capacitive conductivities may not be taken intoaccount. For this purpose it is enough to specify zero values forthe corresponding parameters.

 The initial data for calculating the parametersof the line equivalent circuit are:

  • the length of the line, expressed in [m] or [km];

  • active and inductive resistances per unit length, expressed in \( \frac{\mathrm{м}\mathrm{к}\mathrm{С}\mathrm{м}}{м};\frac{\mathrm{м}\mathrm{к}\mathrm{С}\mathrm{м}}{\mathrm{к}\mathrm{м}};\frac{\mathrm{м}\mathrm{к}\mathrm{С}\mathrm{м}}{100\mathrm{к}\mathrm{м}}\)

  • active and capacitive conductivities per unit length, expressed in \(\frac{\mathrm{м}\mathrm{к}\mathrm{С}\mathrm{м}}{м};\frac{\mathrm{м}\mathrm{к}\mathrm{С}\mathrm{м}}{\mathrm{к}\mathrm{м}};\frac{\mathrm{м}\mathrm{к}\mathrm{С}\mathrm{м}}{100\mathrm{к}\mathrm{м}}\)

Note

In the next versions it is possible to add calculation of line parametersper unit length depending on the line configuration (conductor cross-section,distance between phases, etc.), as well as simulation of corona lossesand line charging power by setting the corresponding power.

1.  Properties#

Property

Default value

Description

Units of measurement

Line length

100

-

-

Length units:
m;
km

km

-

-

Resistance

0.0365

-

Ohm per unit length

Inductive resistance

0.323

-

Ohm per unit length

Сapacitive susceptance

3.46

-

µS per unit length

Conductance

0.027

-

µS per unit length

Order of magnitude of linear electrical parameter per unit length:
m;
km;
100km

km

-

-

2.  Inputs and outputs#

Parameters

Input/Output

Description

Units of measurement

Port type

Input

Input

-

-

Electrocity

Voltage at the end of the power line

Output

-

V

Electrocity

In order to see the connection capabilities of the block, you need to go to page Description of block ports