Three-phase three winding free configurable transformer#

block

Block appearance in REPEAT VISION#

 The Three-phase three winding free configurable transformer block is a model of a three-phase three-winding transformer assembled from three single-phase three-winding transformers.

 An important feature of this model is the ability to set an arbitrary configuration of the connection of the transformer windings.

 The model has various ways of model parameters:

  1. SI system. In this case, parameters of the primary, secondary and tertiary windings are set separately: rated phase voltages, [V], resistance, [Ohm] and inductance, [H].

Important

The transformation ratio is calculated from phase voltages.

 If windings are connected in the same circuit, then the ratio of phase voltages will be equal to the ratio of linear. In this case, if circuits are different, it is necessary to convert from linear to phase values. An example of such conversion is given in the table below.

Winding connection method (primary-secondary)

Transformation ratio

Star-Star-Star

K\(_1\)=\(\frac{U_{2ном Ф}}{U_{1ном Ф}}\)=\(\frac{U_{2ном}}{\sqrt {3}}\cdot \frac{\sqrt {3}}{U_{1ном}}=\frac{U_{2ном}}{U_{1ном}};\)
K\(_2\)=\(\frac{U_{3ном Ф}}{U_{1ном Ф}}\)=\(\frac{U_{3ном}}{\sqrt {3}}\cdot \frac{\sqrt {3}}{U_{1ном}}=\frac{U_{3ном}}{U_{1ном}}\)

Star-Triangle I-Star

K\(_1\)=\(\frac{U_{2ном Ф}}{U_{1ном Ф}}\)=\(\frac{U_{2ном}}{\sqrt {3}}\cdot \frac{1}{U_{1ном}}=\frac{U_{2ном}}{\sqrt {3} \cdot U_{1ном}};\)
K\(_2\)=\(\frac{U_{3ном Ф}}{U_{1ном Ф}}\)=\(\frac{U_{3ном}}{\sqrt {3}}\cdot \frac{\sqrt {3}}{U_{1ном}}=\frac{U_{3ном}}{U_{1ном}};\)

Star-Star-Triangle I

K\(_1\)=\(\frac{U_{2ном Ф}}{U_{1ном Ф}}\)=\(\frac{U_{2ном}}{\sqrt {3}}\cdot \frac{\sqrt {3}}{U_{1ном}}=\frac{U_{2ном}}{U_{1ном}};\)
K\(_2\)=\(\frac{U_{3ном Ф}}{U_{1ном Ф}}\)=\(\frac{U_{3ном}}{\sqrt {3}}\cdot \frac{{1}}{U_{1ном}}=\frac{U_{3ном}}{\sqrt {3} \cdot U_{1ном}}\)

  1. Relative units. The calculation procedure for this case is described in the corresponding article.

Important

Additional parameters have been entered in this block: base strains.

 They are used to calculate basic values when transferring from relative units to SI system. The strains specified in winding parameters shall be phase (or linear in case of the same methods of connection of the primary and secondary windings), since they are used to calculate the transformation ratios.

  1. Catalog data. The calculation procedure for this case is described in the article.

Important

Additional parameters have been entered in this block: base strains.

 They are used to calculate basic values when transferring from relative units (in which the calculation is initially made from catalog parameters) to SI system. The strains specified as nominal shall be phase (or linear in case of the same methods of connection of the windings), since they are used to calculate the transformation ratios.

1.  Properties#

Property

Default Value

Description

Units of measurement

Method of specifying model parameters:
SI;
PU;
Specification

SI

-

-

Primary winding parameters, U\(_{1ф}\); R\(_1\); L\(_1\)

230000.0;4.3218;0.45856;

Available, when Method of specifying model parameters - SI

V; Ohm; H

Secondary winding parameters, U\(_{2ф}\); R\(_2\); L\(_2\)

115000.0;0.7938;0.084225;

Available, when Method of specifying model parameters - SI

V; Ohm; H

Tertiary winding parameters, U\(_{3ф}\); R\(_3\); L\(_3\)

35000.0;0.7938;0.084225;

Available, when Method of specifying model parameters - SI

V; Ohm; H

Magnetizing branch parameters, R\(_m\); L\(_m\)

1080400.0;2866.0;

Available, when Method of specifying model parameters - SI

Ohm; H

Nominal power

2.5e8

Available, when Method of specifying model parameters - PU or Specification

VA

Nominal frequency

50.0

Available, when Method of specifying model parameters - PU or Specification

Hz

Primary winding parameters, U\(_{1ф}\); R\(_1\); L\(_1\)

230000.0;0.02;0.68;

Available, when Method of specifying model parameters - PU

V; r.u.; r.u.

Secondary winding parameters, U\(_{2ф}\); R\(_2\); L\(_2\)

115000.0;0.02;0.68;

Available, when Method of specifying model parameters - PU

V; r.u.; r.u.

Tertiary winding parameters, U\(_{3ф}\); R\(_3\); L\(_3\)

35000.0;0.02;0.68;

Available, when Method of specifying model parameters - PU

V; r.u.; r.u.

Magnetizing branch parameters, R\(_m\); L\(_m\)

500.0;500.0;

-

r.u; r.u.

Nominal voltage of primary winding

230000.0

Available, when Method of specifying model parameters - Specification

V

Nominal voltage of secondary winding

115000.0

Available, when Method of specifying model parameters - Specification

V

Nominal voltage of tertiary winding

115000.0

Available, when Method of specifying model parameters - Specification

V

Nominal HV - LV short-circuit losses

35000.0

Available, when Method of specifying model parameters - Specification

W

Nominal HV -MV short-circuit losses

35000.0

Available, when Method of specifying model parameters - Specification

W

Nominal HV - LV short-circuit losses

35000.0

Available, when Method of specifying model parameters - Specification

W

Nominal HV - LV impedance voltage

10.5

Available, when Method of specifying model parameters - Specification

%

Nominal HV - MV impedance voltage

10.5

Available, when Method of specifying model parameters - Specification

%

Nominal MV - LV impedance voltage

10.5

Available, when Method of specifying model parameters - Specification

%

Nominal no load losses

10000.0

Available, when Method of specifying model parameters - Specification

W

Nominal no load current

0.5

Available, when Method of specifying model parameters - Specification

%

Initial currents of phase A windings, I\(_{1А}\); I\(_{2А}\); I\(_{3А}\)

0.0;0.0;0.0;

-

А

Initial currents of phase B windings, I\(_{1B}\); I\(_{2B}\); I\(_{3B}\)

0.0;0.0;0.0;

-

А

Initial currents of phase C windings, I\(_{1C}\); I\(_{2C}\); I\(_{3C}\)

0.0;0.0;0.0;

-

А

Initial values of phase A magnetization branch current and voltage, I\(_{MА}\); U\(_{MА}\)

0.0;0.0;

-

А; V

Initial values of phase B magnetization branch current and voltage, I\(_{MB}\); U\(_{MB}\)

0.0;0.0;

-

А; V

Initial values of phase C magnetization branch current and voltage, I\(_{MC}\); U\(_{MC}\)

0.0;0.0;

-

А; V

Base voltage of primary winding

230000.0

Available, when Method of specifying model parameters - PU

V

Base voltage of secondary winding

115000.0

Available, when Method of specifying model parameters - PU

V

Base voltage of tertiary winding

35000.0

Available, when Method of specifying model parameters - PU

V

2.  Inputs and outputs#

Parameters

Input/Output

Description

Units of measurement

Port type

А

Input

-

-

Electronics

X

Output

-

-

Electronics

B

Input

-

-

Electronics

Y

Output

-

-

Electronics

C

Input

-

-

Electronics

Z

Output

-

-

Electronics

x\(_2\)

Output

-

-

Electronics

a\(_2\)

Input

-

-

Electronics

y\(_2\)

Output

-

-

Electronics

b\(_2\)

Input

-

-

Electronics

z\(_2\)

Output

-

-

Electronics

c\(_2\)

Input

-

-

Electronics

x\(_3\)

Output

-

-

Electronics

a\(_3\)

Input

-

-

Electronics

y\(_3\)

Output

-

-

Electronics

b\(_3\)

Input

-

-

Electronics

z\(_3\)

Output

-

-

Electronics

c\(_3\)

Input

-

-

Electronics

In order to see the connection capabilities of the block, you need to go to page Description of block ports