Automatic excitation control (AEC) is a device that acts on the excitation system of synchronous machines to maintain the voltage in the electrical network at a given level.

 Regulators of the ARV-SDP1 type currently make up the majority of “strong action” regulators used at power facilities of the SES/UES.[1]

 According to the diagram (see Fig. 1 below) the mathematical model of the regulator is written as (1) :

(1)#\[\Delta U_{АРВ}= W_{БУ}(p) \cdot [W_{БН}(p)\cdot (К_{БН} \cdot \Delta U_Г+ K_{БРТ-1} \cdot \Delta I_{RГ}+K_{БРТ-2}\cdot \Delta I_{R\Sigma})(K_{0U}+K_{1U}\cdot W_{ДН(p)})+K_{1If}\cdot W_{БТ}(p)\cdot \Delta I_f - W_{БЧЗ}(p)\cdot (K_{0f}+K_{1f} \cdot W_{ДЧ}(p))\cdot \Delta \omega + W_{ЖОС}(p)\cdot K_{ЖОС}\cdot \Delta U_f],[В]\]

where \(K_{1U}, K_{0f}, K_{1f}, K_{1If}\) are weighting coefficients, [V/V]. Their values ​​depend linearly on the position of the switches.

Fig. 1. Structural diagram of the SDP1 AEC

Fig. 1. Structural diagram of the SDP1 AEC#

1.  Properties#

Property

Default Value

Description

Units of measurement

Hard feedback channel coefficient

1

–

–

Rotor current derivative gain

5

–

–

Frequency gain

2

–

–

Frequency derivative gain

5

–

–

Voltage gain factor

50

–

–

Voltage derivative gain

5

–

–

Reactive current block coefficient 1

3

–

–

Reactive current block coefficient 2

-10

–

–

Time constant of the voltage block

0.264

–

s

Voltage block gain

2

–

–

Gain of the differentiating link of the voltage block

0.264

–

–

Time constant of the differentiating link of the voltage block

0.264

–

s

Block gain

50

–

–

Minimum value of AEC voltage

-6

–

V

Maximum value of AEC voltage

6

–

V

2.  Inputs and outputs#

Parameters

Input/Output

Description

Units of measurement

Port type

Отклонение напряжения возбуждения

Input

–

V

Automation

Excitation current deviation

Input

–

A

Automation

Generator speed deviation

Input

–

rpm

Automation

Deviation of reactive current of generator stator

Input

–

A

Automation

Generator voltage deviation

Input

–

V

Automation

Deviation of reactive current of a group of generators

Input

–

A

Automation

Voltage AEC

Output

–

V

Automation