Current-limiting reactor#
Block appearance in REPEAT VISION#
The Current-limiting reactor block models a three-phase current-limiting reactor, which is connected in series in an electric circuit to limit SC currents.
Mathematically, the block is a symmetrical three-phase series resistance, the complex resistance of one phase of which is determined by the expression (1) :
where:
\(R\) – active resistance of one phase of the reactor, [Ohm];
\(X\) – inductive resistance of one phase of the reactor, specified in the property Nominal inductive resistance, [Ohm].
When the Incorporate active power losses property is enabled, the active resistance of one phase of the reactor is determined by the formula (2):
where:
\(\Delta P_{nom}\) – nominal active power losses, total for three phases, [kW];
\(I_{nom}\) – nominal current of the reactor, [A].
When the Incorporate active power losses property is disabled, the active resistance of one phase of the reactor is assumed to be negligible.
1. Properties#
Property |
Default Value |
Description |
Units of measurement |
|---|---|---|---|
0.45 |
Inductive reactance per reactor phase |
Ohm |
|
Off |
– |
– |
|
Rated current |
1000.0 |
Available, when |
А |
Rated active power losses, available, when |
19.8 |
Total active power losses of all three reactor phases at rated current |
kW |
2. Inputs and outputs#
Parameters |
Input/Output |
Description |
Units of measurement |
Port type |
|---|---|---|---|---|
Input |
Input |
– |
– |
Electrocity |
Current |
Output |
– |
А |
Electrocity |
In order to see the connection capabilities of the block, you need to go to page Description of block ports