Current-limiting reactor#

block

Block appearance in REPEAT VISION#

 The Current-limiting reactor block models a three-phase current-limiting reactor, which is connected in series in an electric circuit to limit SC currents.

 Mathematically, the block is a symmetrical three-phase series resistance, the complex resistance of one phase of which is determined by the expression (1) :

(1)#\[Z=R+j \cdot X\]

where:

 \(R\) – active resistance of one phase of the reactor, [Ohm];

 \(X\) – inductive resistance of one phase of the reactor, specified in the property Nominal inductive resistance, [Ohm].

 When the Incorporate active power losses property is enabled, the active resistance of one phase of the reactor is determined by the formula (2):

(2)#\[R=\frac{\Delta P_{ном} \cdot 10^3}{3 \cdot I^2_{ном}}\]

where:

 \(\Delta P_{nom}\) – nominal active power losses, total for three phases, [kW];

 \(I_{nom}\) – nominal current of the reactor, [A].

 When the Incorporate active power losses property is disabled, the active resistance of one phase of the reactor is assumed to be negligible.

1.  Properties#

Property

Default Value

Description

Units of measurement

Rated inductive reactance

0.45

Inductive reactance per reactor phase

Ohm

Incorporate active power losses

Off

–

–

Rated current

1000.0

Available, when Incorporate active power losses – On

А

Rated active power losses, available, when Incorporate active power losses – On

19.8

Total active power losses of all three reactor phases at rated current

kW

2.  Inputs and outputs#

Parameters

Input/Output

Description

Units of measurement

Port type

Input

Input

–

–

Electrocity

Current

Output

–

А

Electrocity

In order to see the connection capabilities of the block, you need to go to page Description of block ports